Milne Point North Slope Alaska

3,000 KVAR, 15 kV, Automatic Harmonic Filter

Overloaded generators, excessive harmonics and the need for additional system capacity resulted in the installation of two 15 kV 3.0 MVAR power factor correction and harmonic filter units. These units included many special features to allow for operation in the severe Arctic environment. Examples are 5 kW 480 Vac industrial heaters, special control scheme that insured the interior temperature was satisfactory for operation and -110 degree gasketing material. Once installed the harmonics were reduced to below IEEE 519 standards and the power factor was corrected allowing for additional system capacity and future electrical expansion


 


 

 